苏州远通电缆有限公司
主营产品:
2023年11月21日 10:41
产品标准
本产品按GB12527-90《额定电压0.6/1KV及以下架空绝缘电缆》及IEC60502《额定电压1-30KV挤包绝缘电力电缆及附件》等标准制造。
The product is manufactured according to the standards of GB 12527-90《Aerial insulated cables of rated voltages up to and including 1 KV》and IEC60502《Extruded solid dielectric power cables for rated voltages from 1KV to 30 KV》。
使用特性
额定电压Uo/U为0.6/1KV.
Rated voltage Uo/u:0.6/1KV.
电缆导体的长期允许工作不超过湿度:
聚氯乙烯、聚乙烯绝缘架空电缆:70℃;
交联聚乙烯绝缘架空电缆:90℃。
Max.permissible continuous temperature:
PVC、PE insulated aerial cables:70℃
XLPE insulated aerial cables:90℃.
短路时(***长持续时间不超过5秒)电缆导体的温度应不超过:
聚氯乙烯绝缘架空电缆:160℃;
聚乙烯绝缘架空电缆:130℃;
交联聚乙烯绝缘架空电缆:250℃。
Max.short-circuit temperature of the conductor shall not execeed:
PVC insulated aerial cables: 160℃;
PE insulated aerial cables: 130℃;
XLPE insulated aerial cables: 250℃.
电缆敷设时环境温度应不低于-20℃。than 6 times the diameter of cables .
The installation ambient temperature should not below -20℃。
电缆的允许弯曲半径:www.0512dxdl.com
电缆外径(D)小于25mm时,应不小于电缆外径的4倍;
电缆外径(D)等于或大于25mm时,应不小于电缆外径的6倍。
The bending radius of cables are recommend as follows:
When the diameter of cables less than 25 mm : not less than 4 times the diameter of cables ;
When the diameter of cables not less than 25 mm : not less
当电缆使用于交流系统时,电缆的额定电压至少应等于该系统的额定电压;当电缆使用地直流系统时,该系统的额定电压应不大于电缆额定电压的1.5倍。
When the cables use in alternating current system, rated voltage of cables should be at least equal the rated voltage of the system; When the cables use in direct current system,rated voltage should be not greater than 1.5 times of the rated voltage of the cables .