产品介绍 产品信息 名称: CXF60-N 品牌:TELAU The CXF60-N series universal coaxial surge protector is designed to protect radio systems up to 500MHz. The CXF60-N series employs a circuity that offers on ultra-sharp clamping that eliminates transients. Low Frequency Coaxial Surge Protection -6 KA IEC 61000-4-5(8/20μs) -6 A DC continuous -up to 60 VDC(any polarity)user voltage -ROHS 6 compliant -Bi-directional,series installed -Waterproof Characteristics CITEL series CXF60-N series Max RMS input power 45 dBm Max peak input power 50 dBm Nomial impedance 50 Ohms User Current 6 A DC continuous User Voltage up to 60 VDC any polarity Max Surge 6 KA IEC 61000-4-5(8/20μs waveform) IEC standard Meets IEC standard 60529 IP67 Operating temperature -50℃to+85℃ Humidity 5-95% non-condensing internal,up to 100% external Bellcore standard TA-NWT-000487 procedure4.11RoHS 6 compliant Connection method series(Bi-directional) connectors N-Male to N-Female Bulkhead&N-Female to N-Female Bulkhead The efficiency of coaxial protectors is highly dependent on proper installation, in
particular their connection to the grounding network of the installation.
The following installation rules must be strictly observed to ensure proper
grounding:
Equipotential bonding network: all of the bonding conductors of the
installation must be interconnected and connected to the installation
grounding network.
Optimized connection of the protector to the bonding network: to reduce the
residual voltages during lightning discharge currents, the connection of the
protector to the bonding network must be as short as possible (less than
50cm or 19.7in) and has a proper cross section (at least 12 AWG or 4 mm²).
The «feed through mounting» method is ideal as it meets all of these
requirements.
Warning: for good contact, carefully remove all painted or insulated coatings.
Location of the protectors: they should preferably be placed at the entrance of
the installation (to limit the penetration of lightning currents) and as close as
possible to the sensitive equipment (to enhance protection).
Feed through mounting
Direct mounting of the surge protector on the grounded frame at the
installation entrance :
Perfect connection to the bonding network
Best location (conduction of the surge currents at the entrance of the
installation)
Good mechanical withstand.
Alternative mounting
Connect to the bonding network via grounding wire (12 AWG or 4 mm²
minimum and shortest length possible).
The operation of maintenance and repair on the Isolated Loop Circuit Protector
shall be returned to the manufacturer for remplacement 产品特写图