DG TNS H230 400 LI SPD according to EN 61643-11 Type 2 SPD according to IEC 61643-1 Class II Nominal a.c. voltage 230/400 V Max. continuous operating a.c. voltage [UC] 275 V Nominal discharge current (8/20 µs) [In] 20 kA Max. discharge current (8/20 µs) [Imax] 65 kA Voltage protection level [UP] ≤ 1.25 kV Voltage protection level for 5 kA [UP] ≤ 1 kV Response time [tA] ≤ 25 ns Max. mains-side overcurrent protection 160 A gL/gG Short circuit withstand capability for max. mains-side overcurrent protection 20 kArms Temporary overvoltage (TOV) [UT] 335 V / 5 sec. Operating temperature range -40°C...+55°C Cross-sectional area (min.) 1.5 mm2 solid/flexible Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible For mounting on 35 mm DIN rail acc. to EN 60715 Enclosure material red thermoplastic, UL 94 V-0 Degree of protection IP 20 Dimension 4 mods., DIN 4 Approvals, Certifications KEMA Type of remote signalling contact changeover contact Type of remote signalling contact changeover contact Switching capacity a.c. 250 V/0.5 A Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible Indication of disconnector green-yellow-red PU 1 pcs. ordering information Type DG TNS H230 400 LI Part No. 950 170 Packing unit 1 pc(s)